Solar Metrix Pro

Solar System Size Calculator Guide: Location-Based Sizing, Peak Load and DC/AC Ratio

This calculator does not apply a fixed number and hope. It takes your metered consumption, then resolves it against the real historical sun and temperature record for your exact coordinates — five years of it, integrated hour by hour. This guide explains how that works, why location matters more than any other input, and how to read the two figures people most often confuse.

9 min read Updated September 2026 open the calculator →
In one minute

Two inputs decide everything: your metered monthly kilowatt-hours, and your location. There is no coverage slider — solar is always sized to cover 100% of the kWh you type, and if you want a smaller array you enter a smaller number.

Location is the core of the tool. Without coordinates it falls back to a generic 4 peak-sun-hour yield of 1,460 kWh/kWp/year — the same for everywhere on earth. With coordinates it fetches five complete years of historical daily irradiance plus a year of hourly tilted irradiance and temperature for that exact spot, and integrates the result hour by hour.

Two different numbers come out. Energy (kWh) sizes the array. Peak power (kW) sizes the inverter, the wiring and any battery. They are not interchangeable, and the calculator keeps them apart.

Input method 1: direct kWh — and why it wins

The calculator's preferred input is the monthly kilowatt-hours figure from your electricity bill or meter. This is the sizing input.

Here is the part that surprises most people: both input methods run through exactly the same formula. The appliance method is not a different, cleverer calculation — it is the same calculation fed with an estimate instead of a measurement. Internally both collapse to a single number, monthly kWh, which is then multiplied by 12 for annual use.

So the only thing the method choice changes is how trustworthy that number is.

  • A meter total is measured. It already contains everything real: the extra draw of an inverter sitting at part load, a fridge's genuine duty cycle, the hours you were actually home, the days you ran the washing machine. All of that is already baked in.
  • An appliance list is a sum of estimates. Each row multiplies rated nameplate watts by hours by a usage factor. Rated power is not average power — the calculator itself warns that an inverter air conditioner or a modern fridge can differ considerably from its label. Every row you add is another chance to be wrong, and the errors all point the same way if you are guessing.

This is why the calculator labels the appliance path “Rough estimate” in its own interface. It is not a lesser method, it is a method with a wider error bar.

When the appliance method is still the right choice

  • You genuinely do not know your kWh. No bill, no meter read, no idea. A list of what you run is far better than nothing, and it is honest about being approximate.
  • You want to understand how sizing works. A list forces you to account for every load. It is the best way to build intuition, and it is why the appliance path is worth understanding even if you never use it to buy.
  • You want your peak load. Only an appliance list can produce it, because peak power is a property of individual appliances, not of a monthly total. See the next-but-one section.
Why the calculator refuses to average the two. If you enter a bill figure and build an appliance list and they disagree — say 110 units a month from the appliances against 1,200 from the bill — then one of them is wrong, and averaging a wrong estimate with a right one still gives a wrong answer. The calculator shows both in a cross-check, tells you which is more reliable, and sizes from the one you choose. It never blends them for you.

Why your location is the core of this calculator

Ask how much a 1 kW solar array produces in a year and the honest answer is it depends where it is. Four separate things drive that, and all four are available as measured data for any point on earth:

1. Sun hours differ by region

This is the big one. Even the calculator's coarse fallback bands — used only when weather data cannot be fetched — span a wide range:

Latitude bandPlanning yield
Tropics (under 20°)1,740 kWh/kWp/year
Arid / sub-tropical (20–35°)1,620 kWh/kWp/year
Temperate (35–50°)1,320 kWh/kWp/year
High latitudes (50° and above)1,020 kWh/kWp/year
No location entered1,460 kWh/kWp/year (4 peak sun hours a day)

That is roughly a 70% spread between the top and bottom band. A system sized with one number applied to the wrong band can be badly oversized or badly undersized, and you would have no way of knowing.

2. Weather is different every year

A single bad year is not a climate. That is why the calculator asks for the last five complete calendar years of daily irradiance, averages them month by month, and then scales that long-term profile onto the most recent year — with the scaling clamped so one freak year cannot distort the answer. The result is a five-year mean that still reflects what is happening now.

3. Temperature derates the panels

Panels are rated at 25 °C and produce less as they get hotter. The calculator models this hour by hour rather than applying a flat haircut: it estimates the cell temperature from the ambient temperature and the irradiance hitting the panel, then applies a temperature coefficient of about −0.35% per °C above 25. A hot, clear site therefore produces measurably less than a mild one with the same sunshine — and the calculator knows that without being told.

4. The angle of the sun changes

Sunlight does not arrive vertically, and the angle shifts through the day and through the year. The calculator requests hourly global tilted irradiance rather than a daily horizontal total, so the geometry of the sun is already inside the data. It derives a sensible tilt from your latitude automatically (about 0.87× your latitude in degrees) and asks the weather service for irradiance at that tilt.

So what is the actual advantage? Most calculators pick a national or continental yield figure from a lookup table and call it done. This one asks the historical archive what the sky actually did at your coordinates, then adds up the energy hour by hour. That is the difference between a guess with a decimal point in it and a measurement. The result is a normal kWp number — the difference is that you can trust where it came from.

Where the location data comes from, honestly stated

For transparency, because a tool that claims to be location-precise should say what it is actually precise about:

  • The weather fetch uses the free Open-Meteo historical archive, no API key, covering the last five complete years.
  • Without coordinates, or if that fetch fails, the calculator falls back to the latitude bands in the table above — and it labels which of the two it used, in a badge on the result. It never pretends a fallback is live data.
  • Tilt is derived from latitude, not entered. Azimuth is fixed to due south. If you are in the southern hemisphere the derived tilt is still correct, but the fetch is not mirrored north-to-south, so treat a southern-hemisphere result as a good planning figure rather than a precise one.
  • System losses are a flat allowance (about 8% plus 2% soiling) rather than a per-component calculation, and shading at your specific roof is not modelled. Use the Energy Yield Estimation tool for a bankable production figure that accounts for orientation and shading.
The fallback is a fallback. With no location the calculator applies 4 peak sun hours a day, which is a reasonable middle-of-the-road planning number and completely ignores where you are. If the result page shows “Basis: rule of thumb” rather than a weather-data badge, you are looking at a generic number. Enter your coordinates to change that.

Peak load vs total load: the two numbers people confuse

These are genuinely different quantities that answer different questions, and the calculator keeps them separate on purpose.

Total loadPeak load
UnitkWh per monthkW, at one instant
Question it answersHow much energy do I need over time?How much power do I need all at once?
What it sizesThe solar array, in kWpThe inverter, the cable, and any battery backup
How to get itYour electricity bill or meterSum your appliances' running watts

A concrete comparison makes the difference obvious. Two homes both consume 600 kWh a month:

  • Home A peaks at 2.4 kW — a fridge, some lights, a router, a television.
  • Home B peaks at 9.8 kW — the same essentials plus a 1.5-tonne air conditioner, a water pump and a washing machine starting together.

Both homes need exactly the same solar array, because they consume the same energy. Home B needs a materially larger inverter, thicker cable, and a bigger battery if it wants to ride through an outage. Same array, very different hardware around it.

What this calculator does with peak load. It computes it and shows it when you build an appliance list, because it is genuinely useful information. It does not use it in any result — the array comes from energy, and the inverter comes from the DC/AC ratio described below. That is a deliberate separation, not an oversight: sizing the inverter on peak load would fight against the DC/AC design, because you would end up with an inverter far larger than the array can justify. The peak figure is handed to you so an installer can check the inverter, the wiring and any backup system against the worst moment.

Inverter selection: the DC/AC ratio

The DC/AC ratio is simply:

DC/AC ratio = array DC nameplate (kWp) ÷ inverter AC nameplate (kW)

example: 10 kWp array, 8 kW inverter → ratio = 10 ÷ 8 = 1.25

“A smaller inverter can handle more DC” — what that really means

This is the single most misread idea in solar, so it is worth being precise. When people say a smaller inverter “handles” more DC than its rating, the implication is that it absorbs or stores the surplus. It does neither.

The array genuinely can push more power than the inverter is rated to convert — that is what putting DC in and AC out means. The inverter converts what it can and limits its output. The gap between what the array could produce and what the inverter will emit is clipping, and the energy in that gap is energy you paid for and do not get.

So a DC/AC ratio above 1.0 is a deliberate trade, not free capacity. It buys you two real things:

  • Better efficiency through the day. Inverters are most efficient somewhere around 30–100% of their nameplate load. A slightly smaller inverter climbs into that band earlier in the morning and stays in it longer, so more of the day's energy is converted at high efficiency. Total daily harvest usually rises even though instantaneous output is capped.
  • Lower cost. You buy fewer kW of inverter, and the inverter is typically the second most expensive item after the panels.

And one real cost:

  • Clipping in strong sun. On a clear summer midday, once array output exceeds the inverter's limit, everything above it is lost for that hour. This is why the calculator flags higher ratios as aggressive rather than simply better.

There is also a practical point in favour of the smaller inverter: on a partly cloudy day the array rarely approaches its peak, so a smaller unit is rarely the thing limiting you. Oversizing is insurance against a clear sky you may only get a few dozen times a year.

The bands the calculator uses

For inverters up to 100 kW:

DC/AC ratioVerdictWhat it means
1.15 – 1.35PreferredThe array is 15–35% larger than the inverter. The normal, well-engineered design.
1.05 – 1.15ConservativeVery little clipping risk. Costs a little in daily yield.
Below 1.05Inverter relatively oversizedYou have paid for inverter capacity the array can never use. It will spend much of its life at very low load, which is its least efficient region.
1.35 – 1.50Aggressive — investigate clippingReal clipping losses in strong sun. Sometimes deliberate, sometimes a mistake.
Above 1.50Excessive DC oversizingYou are discarding meaningful energy and paying for panels that get clipped.

Above 100 kW the preferred band tightens to 1.05 – 1.15, because large industrial inverters stay efficient closer to full load and need less help reaching it.

How the calculator picks one

It evaluates every standard inverter size against your array, discards any that fall outside the preferred band, and from what remains picks the one whose ratio is closest to 1.25. If nothing lands in the preferred band it falls back to the nearest conservative or aggressive candidate, and shows the two sizes either side of its choice so you can see the trade-off.

Worked example from a real run — 850 kWh/month in Lahore, 600 W panels:

monthly use     850 kWh → annual 10,200 kWh
location yield   ~1,537 kWh/kWp/year (weather data, Lahore)
required        10,200 ÷ 1,537 = 6.6 kWp
whole panels    6.6 kWp ÷ 0.600 kW = 11 → round up to 12 panels
practical array  12 × 600 W = 7.20 kWp
inverter           7.20 ÷ 6 kW = ratio 1.20 → preferred band
generation       7.20 × 1,537 ≈ 11,068 kWh/year
The calculator does not compute your clipping loss. It classifies the band and stops, and the label literally says “investigate clipping” rather than pretending to know the answer. It genuinely cannot know it here, because the loss depends on your array's tilt and orientation and on the hourly weather distribution at your site. That is precisely what the Energy Yield Estimation tool models — get a production figure from it before you commit to an aggressive ratio.

The full sizing chain

Everything the calculator does, in order:

1.  consumption    monthly kWh (meter, or appliance estimate)
2.  future load   optional margin added if you expect more usage
3.  annual        monthly kWh × 12
4.  basis         weather data → location yield, else latitude band, else 4 h/day
5.  required     annual kWh ÷ yield (kWh per kWp per year) = kWp required
6.  whole panels round kWp up to a whole number of modules
7.  practical array panels × module wattage = actual kWp
8.  inverter    standard size whose DC/AC ratio sits closest to 1.25
9.  generation   practical kWp × yield = estimated kWh per year
10. module area   planning figure from module dimensions

There is no coverage step, and there is no peak-load step, because neither belongs in the array calculation.

Why there is no coverage target any more. It was only ever a multiplier on the kWh you typed: sizing 1,000 kWh at 60% produced the identical array to sizing 600 kWh at 100%. Two inputs describing one quantity is one input too many — and it carried a genuine bug, because without a location the target was silently ignored, so entering your coordinates could make the recommended system smaller. Solar is now always sized to 100% of the number you enter. To size a smaller array, enter a smaller number.

What this calculator does not do

  • Battery or backup sizing. There is no storage model here at all — no depth of discharge, no autonomy hours, no battery capacity. Use the Battery Backup Calculator.
  • Cost, payback or financial analysis. It holds no price data, so it cannot quote a cost. Use ROI & Payback Analysis.
  • String design. A panel count is not a string design; that needs Voc, Vmp, Isc, Imp and a specific inverter. Use String Sizing.
  • Roof feasibility. It gives a planning module-area figure, not a layout. Use the Roof Space Checker.
  • Clipping loss. As covered above, it classifies the band and leaves the loss to you.

Open the calculator with your numbers

Enter your monthly kWh and your coordinates below. The link carries both into the calculator and runs the sizing as soon as it opens — the panel wattage travels with it too, if you set one.

Launch the calculator pre-filled

Your figures stay in this page. They are only used to build the link you click.

Tip: if you do not know your coordinates, open your map application, right-click your location and copy the latitude and longitude. The calculator only needs the numbers — the city name it shows afterwards is just a label.

Frequently Asked Questions

Why is direct kWh better than listing appliances for sizing solar?
Both methods run through the same formula — monthly kWh times 12 for annual use — so there is no second calculation. The difference is input quality. Your metered total is measured and already includes real behaviour: inverter part-load draw, a fridge's actual duty cycle, the hours you were genuinely home. An appliance list multiplies rated nameplate watts by hours by a usage factor, and rated power is not average power, so every row adds error. The calculator labels the appliance path a rough estimate for that reason. Use it when you do not know your kWh, when you want to understand how sizing works, or when you want your peak load.
Why does my location change the answer so much?
Because a panel's real output depends on sun hours, weather, temperature and the sun's angle, and all four vary enormously by place. The calculator's own fallback latitude bands range from about 1,020 kWh/kWp/year at high latitudes to 1,740 in the tropics — about a 70% spread. With coordinates entered it fetches five complete years of historical daily irradiance plus a year of hourly tilted irradiance and temperature for that exact spot, scales the long-term monthly averages onto the most recent year, and integrates hour by hour, including a temperature derate of about −0.35% per °C above 25. That is the difference between a lookup-table guess and a measurement.
What is the difference between peak load and total load?
Total load is energy over time in kWh per month, and it sizes the solar array. Peak load is the maximum instantaneous power in kW if everything ran at once, and it sizes the inverter, the cable and any battery backup. Two homes both using 600 kWh a month but peaking at 2.4 kW and 9.8 kW need exactly the same array, but the second needs a larger inverter, thicker cable and a bigger battery. The calculator displays peak load from an appliance list but uses it in no result.
What is a DC/AC ratio, and how can a smaller inverter handle more DC power?
The ratio is the array's kWp divided by the inverter's kW; a 10 kWp array on an 8 kW inverter is 1.25. A smaller inverter does not handle or store the extra DC — the array can genuinely push more power than the inverter converts, the inverter limits its AC output, and the difference is clipping. The trade is deliberate: inverters peak in efficiency around 30–100% of nameplate load, so a slightly smaller unit spends more hours in that band, and it costs less per kW. The cost is real energy lost in strong sun, which is why ratios above 1.35 are flagged aggressive.
Does the calculator work out how much energy clipping wastes?
No, and it says so. Above 1.35 it labels the design aggressive and tells you to investigate clipping, but it does not compute a loss, because the answer depends on your array's tilt, orientation and the hourly weather at your site. Use the Energy Yield Estimation tool for a bankable production figure before committing to an aggressive ratio.
Why did the coverage target disappear? How do I size a smaller array now?
A coverage target was only ever a multiplier on the kWh you typed — 1,000 kWh at 60% gave the identical array to 600 kWh at 100%. It also carried a real bug: with no location the target was silently ignored, so adding your coordinates could make the recommended system smaller. Solar is now always sized to 100% of the number you enter; to size a smaller array, enter a smaller monthly kWh figure.
Why is my result slightly over 100% of my usage?
The array is rounded up to a whole number of panels, so it lands a little above the exact requirement. That is deliberate — you cannot buy 11.4 panels — and it is why the reported figure is usually a few percent over rather than exactly 100%. It also means you will over-generate more in summer than winter, so expect to import some power in the low months.

The full calculator map

Each tool answers one question. This is the whole set, and what each one is for — so you can pick the next step instead of opening calculators at random.

Size your own system

Free, instant and interactive — enter your metered kWh and your coordinates, and check the result against the method on this page.

Practical tip: use the average of your last 6–12 bills rather than a single month, so a hot summer or a cold snap does not distort the result — and always enter your location, because that is what separates a real answer from a national average.

This guide explains the Solar Metrix System Size Calculator. Numbers here are illustrations — your results depend on your actual consumption, your coordinates and real weather. Always confirm final sizing with a certified installer.